Javascript is currently disabled. This site requires Javascript to function correctly. Please enable Javascript in your browser!

2 HR Fire Rated Uni-Directional

Safety Storage FS Series - FireShield™

 

Safety Storage FS and FSE Series hazardous material storage buildings utilize the UL Approved      2-Hour uni-directional fire rated wall design that is required for the storage of flammable, combustible, corrosive, and poisonous materials where the storage building is located in close proximity to other buildings and / or property lines.

Safety Storage FS and FSE Series buildings are designed to meet or exceed the current building code requirements in the jurisdiction in which it is delivered.  

 


 

2 Hour Fire Rated Uni-Directional FireShield™

 

2 Hour Fire Rated Uni-Directional FireShield™ - FS Series

Exterior Wall Construction:  Weatherproof 2-hour fire-rated noncombustible construction, with multiple layers of UL Classified fire-resistive gypsum wallboard encased between interior galvannealed steel sheets & exterior welded heavy gauge steel sheets for maximum durability, weather resistance & rigidity. Gypsum wallboard layers are offset with overlapping joints for maximum fire-resistance.

 

Sump Wall Construction:  Weatherproof 2-hour fire-rated noncombustible construction, same as exterior walls, utilizing interior.

   
Roof/Ceiling Construction:  Weatherproof resistant membrane, utilizing interior galvannealed steel sheets & continuously welded heavy gauge steel roof sheets for maximum durability and weather resistance.  Roof/ceiling permanently attached to exterior walls.  

 

2 Hour Fire Rated Uni-Directional FireShield™

with Explosion Relief Panels - FSE Series

 

Explosion Relief Construction: Includes vent panel(s) located on back wall per NFPA 68 requirements.

 

Safety Storage FS and FSE Series - Standard Features 

 

All Safety Storage FS and FSE Series Fire Rated buildings are free-standing, relocatable chemical storage and containment structure.  Safety Storage FS and FSE Series Fire Rated structures are designed to meet critical storage, dispensing, or process applications.  Each structure includes the following components for storage of flammable or combustible liquids and other hazardous materials.

 

Factory Mutual System (FM):  Approved & Labeled.

 

Three-hour fire-rated double door(s):  60”W x 80”H, UL Classified & Labeled, equipped with UL Listed self-closer(s) and UL Listed exterior security lock(s) with keyless interior safety release lever(s).

 

Screened Air Vent(s):  Air inlet vent(s) equipped with UL Classified & Labeled 3-hour rated fire dampers with louvers & screens to provide air flow.  Dampers have a galvanized steel frame, curtain-type galvanized steel blades, and a UL Listed 165°F fusible link.

 

Building Base:  Open channel construction for forklift and/or crane slings and under building inspections.

 

Internal Spill Containment Capacity:  Minimum 30% of total storage capacity.  Surpasses regulatory and Factory Mutual requirements for spill containment.

 

Interior Finish:  High solids, chemical-resistant epoxy coating with a white aliphatic polyurethane topcoat.  

 

Exterior Finish:  High solids, chemical-resistant epoxy undercoat with a heat reflective white aliphatic polyurethane topcoat.

 

Hold-down Brackets (4):   Structural steel angles for bolting to purchaser’s foundation for seismic and wind load anchoring.

 

Static Grounding System:  One (1) exterior grounding connection, one (1) 10-foot long 5/8” diameter copper-clad steel grounding rod, one (1) #4AWG copper conductor, and grounding lug(s).

 

Signage:  D.O.T. hazard classification placard with rust-proof aluminum holder & stainless steel clips; and pressure sensitive NFPA 704 Hazard Rating Sign(s).

 

UL Classified & Labeled:  Equipped with UL Listed self-closer(s) and UL Listed exterior security lock(s) with keyless interior safety release lever(s).

 

Warranty: 15-year structural and 1-year for options



Safety Storage FS and FSE Series - Standard Exterior Dimensions 

 


Safety Storage hazardous material storage buildings are available in a variety of standard sizes to meet your storage capacity requirements.  Our standard sizes are listed below.  

Actual Height:  104” – 120” (Over Height Options Available)

Exterior Nominal Width:  6’, 8’, 10’, 12’, 14’

Exterior Nominal Length:  8’ – 52’ (2’ Increments)

If you have a unique application or layout configuration requirement Safety Storage will utilize their Custom Modular Construction designs to fit your specific needs that are easily assembled on site.

*** Customize your Hazardous Material Storage Building ***

Click on box for information

Contact Us

Expert Consulting - No Charge

Safety is a serious business. The risk from not taking a disciplined approach to developing a plan for hazardous material storage can be devastating.  The Safety Storage process begins with your first visit on our website, to a technical discussion with one of our professional sales representatives, to the specification and design stages of your storage building for the most economical solution, to the delivery of your new containment building, all the way through the final commissioning of a Safety Storage building on your site. We have one objective in mind, and that is to deliver a competitively priced, quality product every time, matched with a great customer experience and your ultimate satisfaction.     

Customers return to us because we make it easy for you, as we work to solve your storage needs that will meet code, and be compliant.  At Safety Storage we sell more than just buildings; we provide engineered* solutions that we support before, during and after the sale.

Lynn Dufek
CEO
Safety Storage


*Safety Storage contracts engineering services for design review and approvals

Asset 1